DC Voltage Drop Calculator
Calculate DC voltage drop over a cable run for remote radios, cameras and injectors, and check the equipment still receives a usable voltage.
Result
Gauge comparison at 1.5 A over 40 m
| Gauge | Drop | At equipment | Max length |
|---|---|---|---|
| 10 AWG | 0.39 V | 47.61 V | 611.6 m |
| 12 AWG | 0.62 V | 47.38 V | 384.9 m |
| 14 AWG | 0.99 V | 47.01 V | 241.9 m |
| 16 AWG | 1.58 V | 46.42 V | 152.3 m |
| 18 AWG | 2.51 V | 45.49 V | 95.7 m |
| 20 AWG | 3.98 V | 44.02 V | 60.2 m |
| 22 AWG | 6.33 V | 41.67 V | 37.9 m |
| 24 AWG | 10.07 V | 37.93 V | 23.8 m |
About DC Voltage Drop Calculator
DC voltage drop is Ohm's law over the round trip of the cable. It is why a radio on a mast browns out at dusk when the heater kicks in, and why 12 V equipment at the end of a long run is a recurring field problem.
Temperature and the numbers that shift
Copper resistance rises about 0.393% per degree Celsius above 20 C. A cable in a sun-exposed conduit at 60 C carries roughly 16% more resistance than the datasheet figure, which is exactly when a marginal design fails — on the hottest afternoon, at peak load. Size for the worst-case ambient you expect, not for a bench measurement, and remember that inrush at power-on can double the steady-state current for a few hundred milliseconds.
The arithmetic
Resistance = ρ × (2 × length) ÷ area, where ρ for copper is 0.0172 Ω·mm²/m. Both conductors carry the current, hence the doubling. Drop = current × resistance. Keep it under 5% of supply voltage for comfort, and never exceed the equipment minimum under peak load - inrush at power-on is often double the steady-state figure.
Common use cases
- Sizing the DC feed for a tower-mounted radio or PTZ camera.
- Deciding between a local injector and a longer DC run.
- Diagnosing equipment that resets under load.
Edge cases and gotchas
- Aluminium conductors have roughly 60% higher resistance than copper for the same area.
- Inrush current at power-on can far exceed steady-state draw - size for the peak.