Rack Power & UPS Runtime Calculator
Calculate rack load, current per phase, UPS runtime and the heat you have to remove - the numbers a colocation order actually needs.
Result
Details
| Item | Value |
|---|---|
| Real power (kW) | 3.2 kW |
| Apparent power (kVA) | 3.368 kVA |
| Power factor | 0.95 |
| Annual energy at full load | 28,032 kWh |
| Runtime at 50% load | 69 minutes |
About Rack Power & UPS Runtime Calculator
Rack power planning needs four numbers: real load in kW, apparent load in kVA, current per feed, and the heat that has to be removed. Colocation is billed and constrained on all of them.
Why the redundant feed must carry everything
In an A+B arrangement each feed normally carries about half the load, and each must be rated for all of it. The moment one PDU, one UPS or one upstream breaker is taken out for maintenance, the survivor carries 100%. Sizing both at 50% is how a planned maintenance window becomes an outage. The same logic applies to the breaker: continuous loads should stay under 80% of its rating, so a 32 A circuit supports about 25 A of steady draw.
kW, kVA and the 80% rule
kW is real power consumed; kVA is what the supply and UPS must deliver, related by power factor. Modern IT power supplies achieve 0.95-0.99, so the gap is small - but UPS and generator ratings are given in kVA and sizing on kW alone undersizes them. Separately, continuous loads should not exceed 80% of breaker rating, so a 32 A circuit supports about 25.6 A of steady draw.
Common use cases
- Specifying power for a colocation order.
- Checking a rack build will not trip its breaker during a feed failure.
- Estimating UPS runtime before adding equipment.
Edge cases and gotchas
- Runtime falls faster than linearly as batteries age - a five-year-old string may deliver half its rated capacity.
- Inrush at power-on can be several times steady-state draw; staggered startup avoids nuisance trips.